Performance investigation of the Afyon geothermal district heating system for building applications: Exergy analysis

Küçük Resim Yok

Tarih

2011

Dergi Başlığı

Dergi ISSN

Cilt Başlığı

Yayıncı

Pergamon-Elsevier Science Ltd

Erişim Hakkı

info:eu-repo/semantics/closedAccess

Özet

This paper deals with an energy and exergy evaluation and modeling of geothermal district heating systems for their system analysis, performance evaluation and optimization. As a comprehensive case study, the Afyon geothermal district heating system (AFJET) in Afyon, Turkey is considered and actual thermal data are collected and employed for analysis. Using actual system data, an evaluation of the district heating system performance, energy and exergy efficiencies, and exergy destructions in the system are conducted in this regard. This study is also conducted to show how energy and exergy efficiencies of the GDHSs will change with the reference temperature and how exergy losses will affect by the temperature difference between the geothermal resource and the supply temperature of the district heating distribution network. In addition, the negative effects of discharge waters of the AFJET are presented. The energy and exergy efficiencies of the entire AFJET are found to be 37.59% and 47.54%, respectively. The results are expected to be helpful to researchers and engineers in the area. Crown Copyright (C) 2010 Published by Elsevier Ltd. All rights reserved.

Açıklama

Anahtar Kelimeler

Geothermal energy, District heating system, Energy analysis, Exergy analysis, Efficiency

Kaynak

Applied Thermal Engineering

WoS Q Değeri

Q1

Scopus Q Değeri

Q1

Cilt

31

Sayı

6-7

Künye