Özet

A thermoeconomic analysis of a water to water heat pump are performed under different condenser andevaporator conditions. Experiments are realized for different volumetric inlet temperatures of 14.4, 17 and 19C? and different volumetric flow rates of 50, 100, 150 lt/h for condenser cooling water. Same inlet temperatureswith condenser cooling water are used for evaporator water inlet, while constant volumetric flow rate of 100 lt/his used for each case. Modified Productive Structure Analysis (MOPSA) is used for thermoeconomic analysis. Itis found that increases in inlet temperature and in volumetric flow rate cause to decrease in both the unit cost ofheat delivered ( H C ) and the unit cost of entropy generation ( S C ). As a result, in the case of inT =14.4 C? and ?= 50 lt/h, H C and S C values are obtained to be 0.0489 $/kWh and 0.0221 $/kWh, respectively, while HC andS C values are obtained to be 0.0385 $/kWh and 0.0175 $/kWh for inT =19 C? and ? = 150 lt/h, respectively.

Açıklama

Anahtar Kelimeler

Kaynak

Journal of Thermal Engineering

WoS Q Değeri

Scopus Q Değeri

Cilt

5

Sayı

3

Künye