SECOND LAW ANALYSIS OF AN ENVIRONMENTALLY FRIENDLY R290/R600/R600a MIXTURE IN A WATER-COOLED HEAT PUMP UNIT

Küçük Resim Yok

Tarih

2014

Dergi Başlığı

Dergi ISSN

Cilt Başlığı

Yayıncı

Turkish Soc Thermal Sciences Technology

Erişim Hakkı

info:eu-repo/semantics/closedAccess

Özet

In this study, second law analysis of environmentally friendly R2901R600/R600a mixture at a rate of 45/46/9 % by mass fraction has been experimentally executed on a water-cooled heat pump as a substitute for HFC134a at varying air and water mass flow rates. Experimental outputs indicate that the heat pump system shows the highest exergy efficiency at 0.040 kg s-1 of water mass flow rate and 0.1 kg s-1 of air mass flow rate running with both R134a and HC mixture. Even though proposed HC mixture has lower COP and rational efficiencies, cooling exergy efficiency of HC mixture is 2-3% better than that of R134a. Higher energy consumption and lower rational efficiencies can be resolved by a hermetic compressor with higher sweep volume which is compatible with pure and mixture hydrocarbons.

Açıklama

Anahtar Kelimeler

R134a, Hydrocarbon Mixture, Heat Pump, Global warming, Second law analysis

Kaynak

Isi Bilimi Ve Teknigi Dergisi-Journal of Thermal Science and Technology

WoS Q Değeri

Q4

Scopus Q Değeri

Cilt

34

Sayı

2

Künye