EXPERIMENTAL INVESTIGATION ON THE EFFECT OF SOIL TYPE TO THE GROUND SOURCE HEAT PUMP'S PERFORMANCE AND ENERGY CONSUMPTION
dc.contributor.author | Acar, Bahadir | |
dc.date.accessioned | 2024-09-29T16:06:48Z | |
dc.date.available | 2024-09-29T16:06:48Z | |
dc.date.issued | 2020 | |
dc.department | Karabük Üniversitesi | en_US |
dc.description.abstract | In the present study an experimental investigation is carried out to predict the performance of ground source heat pump systems with using different soil type under Karabuk prevailing conditions. A series of experiments were conducted on designed and produced experimental test rig. This study examines the effect of five different soil types on the performance and energy consumption of a heat pump. The experimental analysis showed that the evaporator capacity provided by sand was 46% and 42% higher than the capacity provided by red soil at the air-flow rates of 0.087 kg/s and 0.015 kg/s, respectively. In terms of the condenser capacity, sand provided 46% and 30% higher capacity than red soil at the air-flow rates o 0.087 kg/s and 0.015 kg/s, respectively. On the other hand, red soil consumed 8% and 6% less energy than sand at the air-flow rates of 0.087 kg/s and 0.015 kg/s. the capacities provided by other soil types and their energy consumption ranged between these values. In terms of the COP values, red soil provided 6% higher performance than sand and humus soil at the air-flow rates of 0.087 kg/s and 0.015 kg/s. The performance values obtained with other soil types ranged between these values. | en_US |
dc.identifier.doi | 10.2298/TSCI181216028A | |
dc.identifier.endpage | 852 | en_US |
dc.identifier.issn | 0354-9836 | |
dc.identifier.issn | 2334-7163 | |
dc.identifier.issue | 2 | en_US |
dc.identifier.scopus | 2-s2.0-85086735460 | en_US |
dc.identifier.scopusquality | Q3 | en_US |
dc.identifier.startpage | 843 | en_US |
dc.identifier.uri | https://doi.org/10.2298/TSCI181216028A | |
dc.identifier.uri | https://hdl.handle.net/20.500.14619/7034 | |
dc.identifier.volume | 24 | en_US |
dc.identifier.wos | WOS:000522446200017 | en_US |
dc.identifier.wosquality | Q4 | en_US |
dc.indekslendigikaynak | Web of Science | en_US |
dc.indekslendigikaynak | Scopus | en_US |
dc.language.iso | en | en_US |
dc.publisher | Vinca Inst Nuclear Sci | en_US |
dc.relation.ispartof | Thermal Science | en_US |
dc.relation.publicationcategory | Makale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanı | en_US |
dc.rights | info:eu-repo/semantics/openAccess | en_US |
dc.subject | COP | en_US |
dc.subject | energy consumption | en_US |
dc.subject | ground source | en_US |
dc.subject | heat pump | en_US |
dc.subject | soil types | en_US |
dc.title | EXPERIMENTAL INVESTIGATION ON THE EFFECT OF SOIL TYPE TO THE GROUND SOURCE HEAT PUMP'S PERFORMANCE AND ENERGY CONSUMPTION | en_US |
dc.type | Article | en_US |