THERMOECONOMIC ANALYSIS OF A WATER TO WATER HEAT PUMP UNDER DIFFERENT CONDENSER AND EVAPORATOR CONDITIONS
Küçük Resim Yok
Tarih
2019
Dergi Başlığı
Dergi ISSN
Cilt Başlığı
Yayıncı
Yildiz Technical Univ
Erişim Hakkı
info:eu-repo/semantics/openAccess
Özet
A thermoeconomic analysis of a water to water heat pump are performed under different condenser and evaporator conditions. Experiments are realized for different volumetric inlet temperatures of 14.4, 17 and 19 degrees C and different volumetric flow rates of 50, 100, 150 lt/h for condenser cooling water. Same inlet temperatures with condenser cooling water are used for evaporator water inlet, while constant volumetric flow rate of 100 lt/h is used for each case. Modified Productive Structure Analysis (MOPSA) is used for thermoeconomic analysis. It is found that increases in inlet temperature and in volumetric flow rate cause to decrease in both the unit cost of heat delivered (C-H) and the unit cost of entropy generation (C-S). As a result, in the case of T-in =14.4 degrees C and (for all) over dot = 50 lt/h, C-H and C-S values are obtained to be 0.0489 $/kWh and 0.0221 $/kWh, respectively, while C-H and C-S values are obtained to be 0.0385 $/kWh and 0.0175 $/kWh for T-in =19 degrees C and (for all) over dot = 150 lt/h, respectively.
Açıklama
Anahtar Kelimeler
Water to Water Heat Pump, Condenser Cooling Water, Thermoeconomic Analysis, MOPSA
Kaynak
Journal of Thermal Engineering
WoS Q Değeri
N/A
Scopus Q Değeri
Q3
Cilt
5
Sayı
3