THERMOECONOMIC ANALYSIS OF A WATER TO WATER HEAT PUMP UNDER DIFFERENT CONDENSER AND EVAPORATOR CONDITIONS

Küçük Resim Yok

Tarih

2019

Dergi Başlığı

Dergi ISSN

Cilt Başlığı

Yayıncı

Yildiz Technical Univ

Erişim Hakkı

info:eu-repo/semantics/openAccess

Özet

A thermoeconomic analysis of a water to water heat pump are performed under different condenser and evaporator conditions. Experiments are realized for different volumetric inlet temperatures of 14.4, 17 and 19 degrees C and different volumetric flow rates of 50, 100, 150 lt/h for condenser cooling water. Same inlet temperatures with condenser cooling water are used for evaporator water inlet, while constant volumetric flow rate of 100 lt/h is used for each case. Modified Productive Structure Analysis (MOPSA) is used for thermoeconomic analysis. It is found that increases in inlet temperature and in volumetric flow rate cause to decrease in both the unit cost of heat delivered (C-H) and the unit cost of entropy generation (C-S). As a result, in the case of T-in =14.4 degrees C and (for all) over dot = 50 lt/h, C-H and C-S values are obtained to be 0.0489 $/kWh and 0.0221 $/kWh, respectively, while C-H and C-S values are obtained to be 0.0385 $/kWh and 0.0175 $/kWh for T-in =19 degrees C and (for all) over dot = 150 lt/h, respectively.

Açıklama

Anahtar Kelimeler

Water to Water Heat Pump, Condenser Cooling Water, Thermoeconomic Analysis, MOPSA